MCO-5211 | 11
Pin
Function and Value
Comments
6 Output
0: Fault on sync generator 1
1: No fault on sync generator 1
Error status flag for sync generator 1.
Note: During power failure in the changeover, pins 6 and 7 indicate
fault on sync generators both 1 and 2.
7 Output
0: Fault on sync generator 2
1: No fault on sync generator 2
Error _status flag for sync generator 2
Note: During power failure in the changeover, pins 6 and 7 indicate
fault on both sync generators 1 and 2.
8/9 Relay contacts
Connected during fault conditions.
Relay contacts to be used for an externally powered alarm circuit.
The relay contacts are floating. The contact closes whenever an
error is detected, also in case of internal or external power failure.